Overview
Structural
Floor to floor distance, 3,900mm.
Floor loading 4.0kPa, 7.5kPa in designated compactus locations.
Core
Straight core perimeter walls with access/service doors.
Through core passages for direct access on lifts.
Lifts face each other in dedicated lobby. Consistent floor plate
on all rises permits standardisation of office layout.
Tearoom incorporated into core
Dedicated risers are located in centre of core of 2,500mm x 1,070mm.
Floor Layout
Straight perimeter walls.
Core to wall 16m.
Ceilings and Lighting
Ceiling height 2,700mm.
Ceiling zone 900mm.
Ceiling tiles of 1,400mm x 466mm.
Light intensity 400lux. Lights 2 x 36W fluorescent units.
Low brightness diffusers.
Air-conditioning
System type: central plant, variable air volume fan assisted floor
distribution.
18 - 40 variable air volume zones per floor.
Capacities: lighting 16W/m2, population density of one person/10m2.
Tenant equipment 16W/m2.
Condenser water 66W/m2.
Lift
The lift system combines optimum speed performance with extremely
smooth acceleration and deceleration to provide passengers with
a comfortable and efficient ride.
Number of lifts: 25 in all. One dedicated goods lift services tower
and carpark. One goods lift to podium.
Power
Rising mains to office floor distribution boards will be capable
of handling 30W/m²
Typical floor switchboard comprises 60 poles.
Separate proprietor distribution board.
Emergency Power
Standby diesel generators for 100% essential tenant load or 60%
total building load.
Common area light and power
Air-conditioning services and lifts.
Goods Delivery
Loading dock access for goods delivery via goods lift.
Serves all basement car park levels up to level 38.
CCTV, Access Control and Building Automation
CCTV and Access Control Systems are the latest state-of-the-art
technology, with the access control system using proximity
cards. In addition the BMCS is being upgraded.
Access Control Systems to common area doors, lifts, carpark,
entry and exit.
CCTV - covers lobby, carpark, loading dock, building perimeter
plus certain common areas.
Building Automation Systems control lighting, power
plus emergency generator power.
|